Possible faults, causes and elimination methods of knife gate valve:
possible failures | Cause of failure | Elimination method |
Packing leakage | 1. The packing gland is not pressed tightly 2. The filler fails due to long-term use or improper storage | 1. Tighten the nut evenly to compress the packing 2. Replace the packing |
Leakage between sealing surfaces | 1. There is dirt and debris attached to the sealing surface 2. Damaged sealing surface | 1. Clean the dirt and sundries 2. Rework, trim or replace |
Leakage at the connection between the valve body and the bonnet | 1. Uneven tightening of connecting bolts 2. The flange sealing surface is damaged | 1. Tighten evenly 2. Refinish |
The handwheel is inflexible or the gate cannot be opened and closed | 1. The packing is pressed too tightly 2. The stem nut is damaged 3. The thread of the stem nut is severely worn or broken 4. Stem bending | 1. Properly loosen the nut on the packing pressure plate 2. Disassemble and trim threads and remove dirt and debris 3. Replace the stem nut 4. Correct the valve stem |
2021.10
In the process of installing manual knife gate valves, many users have frequent problems due to inexperience. So how to install the manual ...
2024.08
In the field of industrial fluid control,slurry valveIt is a common and important device. However, when we use slurry valves to control pure...
2024.03
Knife type gate valveIt has important applications in industrial fluid control. In order to ensure the safe operation of the entire syst...
Contact Us
Tel: 0577-67962833
Sales: 0577-67371666
Address: Wuxing Industrial Zone, Oubei Town, Yongjia County, Wenzhou City, Zhejiang Province, China
E-mail: 412305565@qq.com